plc automation

Hotline

MTL5544D MTL REPEATER Single Channel POWER SUPPLY MTL5544D

description:MTL5544DRepeater power supplysingle channel, 4/20mA, HART®for 2- or 3-wire transmitters, two outputsThe MTL5544D provides a fully-floating dc supply for energising aconventional 2- or 3-wire 4/20mA transmitter located in a hazardo...
BASIC INFO

MTL5544D REPEATER POWER SUPPLY single channel, 4/20mA, HART for 2- or 3-wire transmitters, two outputs MTL5544D





1.SPECIFICATIONS for MTL5544D

  • MTL5544D
  • Repeater power supply
  • single channel, 4/20mA, HART®
  • for 2- or 3-wire transmitters, two outputs
  • The MTL5544D provides a fully-floating dc supply for energising a
  • conventional 2- or 3-wire 4/20mA transmitter located in a hazardous area and repeats the current in other circuits to drive two safe-area loads
  • For HART 2-wire transmitters, the unit allows bi-directional
  • transmission of digital communication signals superimposed on the
  • 4/20mA loop current
  • Separately powered current sources, such as
  • 4-wire transmitters
  • can be connected but will not support HART communication
  • Shipping weight: 1 kg

MTL5544D REPEATER POWER SUPPLY single channel, 4/20mA, HART for 2- or 3-wire transmitters, two outputs MTL5544D


The MTLx544D provides a fully-floating dc supply for energising a
conventional 2- or 3-wire 4/20mA transmitter located in a hazardous
area, and repeats the current in other circuits to drive two safe-area
loads. For HART 2-wire transmitters, the unit allows bi-directional
transmission of digital communication signals superimposed on the
4/20mA loop current. Separately powered current sources, such
as 4-wire transmitters, can be connected but will not support HART
communication.

MTL5544D REPEATER POWER SUPPLY single channel, 4/20mA, HART for 2- or 3-wire transmitters, two outputs MTL5544D
 

MTL Stock picture

Number of channels:One

Location of transmitter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location

Safe-area output
Signal range: 4 to 20mA
Under/over-range: 0 to 24mA

Safe-area load resistance
@ 24mA: 0 to 360Ω
@ 20mA: 0 to 450Ω
Safe-area circuit output resistance: > 1MΩ

Safe-area circuit ripple
< 50µA peak-to-peak

Hazardous-area input
Signal range: 0 to 24mA (including over-range)
Transmitter voltage: 16.5V at 20mA
Transfer accuracy at 20°C
Better than 15µA

Temperature drift
< 0.8µA/°C
Response time
Settles to within 10% of final value within 50µs

Communications supported
HART (terminals 1 & 2, output Ch 1 only)

MTL5544D REPEATER POWER SUPPLY single channel, 4/20mA, HART for 2- or 3-wire transmitters, two outputs MTL5544D

2. Quality assurance:


1. 100% original product, 100% quality assurance. 
If you find a fake. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt T/T, western union and paypal. If you can not trust us , you can choose to pay it via Aliexpress! 100% make your money safe!
3.SHIPPING:
We can shipping all over the world.via DHL,UPS,Fedex and EMS, the packaging is very safe and strong. if you have any special needs,please notify me.
It will take 3 to 7days to reach in your hands.

 

3.Contact details:

HONGKONG XIEYUAN TECH CO., LIMITED

Email/Skype:sales5@hkxytech.com/amy@whxyauto.com

Whatsapp/Mobile::+8613135657923

Web:www.hkxytech.com/www.plcs-automation.com
 
We mainly supply YOKOGAWA, SIEMENS, EMERSON, ABB, Hesman
ROCKWELL, HONEYWELL, ENDRESS+ HAUSER, PEPPERL+FUCHS, FESTO, PARKER, FLUKE, WEIDMULLER, MTL, SMC,Schneider, , ADVANTECH,MOXA, Hirschmann,US Sensor, Mean Well, Murphy, allen Bradley, YTC. Fisher brands products. brand products.

Any brand products inquiry, feel free to contact me.

Pre:None Next:None