plc automation

Hotline

6ES7334-0KE00-0AB0

description:SIMATIC S7-300, ANALOG MODULE SM 334, OPTICALLY ISOLATED, 4AE/2AA, 12 BIT, 0-10V F. PT100 (CLIMAT RANGE -120 - 155 DEGR.) AND 10 KOHM MEASURING RANGE, 1 X 20 PIN...
BASIC INFO

6ES7334-0KE00-0AB0

6ES7334-0KE00-0AB0

SIMATIC S7-300, ANALOG MODULE SM 334, OPTICALLY ISOLATED, 4AE/2AA, 12 BIT, 0-10V F. PT100 (CLIMAT RANGE -120 - 155 DEGR.) AND 10 KOHM MEASURING RANGE, 1 X 20 PIN
 

Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from supply and load voltage L+ (without load), max. 80 mA
from backplane bus 5 V DC, max. 60 mA
Power loss
Power loss, typ. 2 W
Analog inputs
Number of analog inputs 4
● For voltage measurement 2
● For resistance measurement 4
permissible input voltage for voltage input (destruction limit), max. 20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20)
Cycle time (all channels) max. 85 ms
Input ranges
● Voltage Yes
● Current No
● Thermocouple No
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) 100 kΩ
Input ranges (rated values), resistance thermometer
● Pt 100 Yes; only climatic range
Input ranges (rated values), resistors
● 0 to 10000 ohms Yes
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 30 mA
Output ranges, voltage
● 0 to 10 V Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 2.5 kΩ
● with voltage outputs, capacitive load, max. 1 µF
Cable length
● shielded, max. 100 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit
● Integration time (ms) 16,67 / 20 ms
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit
Settling time
● for resistive load 0.8 ms
● for capacitive load 0.8 ms
Encoder
Connection of signal encoders
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.7 %; 0 to 10V
● Resistance, relative to input range, (+/-) 3.5 %; 10 kOhm
● Resistance thermometer, relative to input range, (+/-) 1 %
● Voltage, relative to output range, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.5 %; 0 to 10V
● Resistance, relative to input range, (+/-) 2.8 %; 10 kOhm
● Resistance thermometer, relative to input range, (+/-) 0.8 %
● Voltage, relative to output range, (+/-) 0.85 %
Interrupts/diagnostics/status information
Alarms No
Diagnostic functions No
Potential separation
Potential separation analog inputs
● between the channels and backplane bus Yes
Potential separation analog outputs
● between the channels and backplane bus Yes
Isolation
Isolation tested with 500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 200 g
last modified: 09/08/2017