6ES7315-6TH13-0AB0

description:SIMATIC S7-300, CPU 315T-2 DP, CENTRAL PROCESSING UNIT FOR PLC AND TECHNOLOGY 256 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S 2. INTERFACE DP(DRIVE), INTEGRATED I/O FOR TECHNOLOGY FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD MIN....
BASIC INFO

6ES7315-6TH13-0AB0

6ES7315-6TH13-0AB0

SIMATIC S7-300, CPU 315T-2 DP, CENTRAL PROCESSING UNIT FOR PLC AND TECHNOLOGY 256 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S 2. INTERFACE DP(DRIVE), INTEGRATED I/O FOR TECHNOLOGY FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD MIN. 8 MB NECESSARY
 

General information
Hardware product version 01
Firmware version CPU: V2.7, integrated technology: V4.1.5
Engineering with
● Programming package STEP 7 V5.4 + SP5 (and higher) and Optional package  S7-Technology V4.2
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2 A min.
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Digital outputs
— Rated value (DC) 24 V; (2L+)
— Reverse polarity protection No; (2L+)
Input current
Current consumption (in no-load operation), typ. 200 mA
Inrush current, typ. 2.5 A
I²t 1 A²·s
Power loss
Power loss, typ. 6 W
Memory
Work memory
● integrated 256 kbyte
● expandable No
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● without battery Yes; Program and data
CPU processing times
for bit operations, typ. 0.1 µs
for bit operations, max. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
● Number, max. 1 023; Number band: 1 to 1023
● Size, max. 64 kbyte
FB
● Number, max. 1 024; Number range: 0 to 2047
● Size, max. 64 kbyte
FC
● Number, max. 1 024; Number range: 0 to 2047
● Size, max. 64 kbyte
OB
● Description see instruction list
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 1; OB 20
● Number of cyclic interrupt OBs 1; OB 35
● Number of process alarm OBs 1; OB 40
● Number of DPV1 alarm OBs 3; OB 55, 56, 57
● Number of isochronous mode OBs 1; OB 61
● Number of technology synchronous alarm OBs 1; OB 65
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 5; OB 80, 82, 85, 86, 87
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 8
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256; Number range: 0 to 255
Retentivity
— adjustable Yes
— preset 8
Counting range
— can be set Yes
— lower limit 0
— upper limit 999
IEC counter
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256; Number range: 0 to 255
Retentivity
— adjustable Yes
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in total All DBs, max. 128 KB
Flag
● Number, max. 2 048 byte
● Retentivity available Yes; MB 0 to MB 2047
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 1 023; From DB 1 to DB 1023
● Size, max. 64 kbyte
● Retentivity adjustable Yes; via non-retain property on DB
● Retentivity preset Yes
Local data
● per priority class, max. 1 024 byte
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
of which distributed
— Inputs 2 048 byte
— Outputs 2 048 byte
Process image
● Inputs, adjustable 2 048 byte
● Outputs, adjustable 2 048 byte
● Inputs, default 128 byte
● Outputs, default 128 byte
Default addresses of the integrated channels
— Digital inputs 66
— Digital outputs 66
Subprocess images
● Number of subprocess images, max. 1
Digital channels
● Inputs 16 384
— of which central 512
● Outputs 16 384
— of which central 512
Analog channels
● Inputs 1 024
— of which central 64
● Outputs 1 024
— of which central 64
Hardware configuration
Number of expansion units, max. 0
Number of DP masters
● integrated 2; 1 DP and 1 DP (drive)
● via CP 2; for DP
Number of operable FMs and CPs (recommended)
● FM 8
● CP, PtP 8
● CP, LAN 10
Rack
● Racks, max. 1
● Modules per rack, max. 8
Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes
● to DP, slave Yes
● in AS, master Yes
● in AS, slave Yes
Digital inputs
Number of digital inputs 4
● of which inputs usable for technological functions 4
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max. 4
— up to 60 °C, max. 4
vertical installation
— up to 40 °C, max. 4
Input voltage
● Rated value (DC) 24 V
● for signal "0" -3 to +5V
● for signal "1" +15 to +30V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for counter/technological functions
— at "0" to "1", max. 10 µs; Typical
— at "1" to "0", max. 10 µs; Typical
Cable length
● shielded, max. 1 000 m
Digital outputs
Number of digital outputs 8
● of which high-speed outputs 8
Functions For technology functions, e.g. high-speed cam switch signals
Short-circuit protection Yes
● Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to 48 V
Controlling a digital input No
Switching capacity of the outputs
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 4 kΩ
Output voltage
● for signal "0", max. 3 V; (2L+)
● for signal "1", min. Rated voltage -2.5 V
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range for 0 to 60 °C, min. 5 mA
● for signal "1" permissible range for 0 to 60 °C, max. 0.6 A
● for signal "0" residual current, max. 0.3 mA
Parallel switching of two outputs
● for uprating No
● for redundant control of a load No
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.2 Hz; According to IEC 60947-5-1, DC-13
● on lamp load, max. 100 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 4 A
— up to 60 °C, max. 3 A
all other mounting positions
— up to 40 °C, max. 3 A
Cable length
● shielded, max. 1 000 m
Analog inputs
Number of analog inputs 0
Analog outputs
Number of analog outputs 0
Encoder
Connectable encoders
● 2-wire sensor No
Interfaces
Number of industrial Ethernet interfaces 0
Number of RS 485 interfaces 2
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● PROFIBUS DP master Yes
● PROFIBUS DP slave Yes
● Point-to-point connection No
MPI
● Number of connections 32
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No; but via CP and loadable FB
— S7 communication, as server Yes; Connection configured on one side only
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes
— S7 communication, as client No; but via CP and loadable FB
— S7 communication, as server Yes; Connection configured on one side only
— Equidistance Yes
— Isochronous mode Yes; OB 61
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— DPV1 Yes
Address area
— Inputs, max. 2 048 byte
— Outputs, max. 2 048 byte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
DP slave
● Transmission rate, max. 12 Mbit/s
● automatic baud rate search No
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— PG/OP communication Yes
— Routing Yes; Only with active interface
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— S7 communication, as client No; but via CP and loadable FB
— S7 communication, as server Yes; Connection configured on one side only
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI No
● PROFIBUS DP master Yes; DP(DRIVE)-Master
● PROFIBUS DP slave No
● Point-to-point connection No
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 64
Services
— PG/OP communication No
— Routing No
— Global data communication No
— S7 basic communication No
— S7 communication No
— Equidistance Yes
— Isochronous mode Yes
— SYNC/FREEZE No
— Activation/deactivation of DP slaves Yes
— DPV1 No
Address area
— Inputs, max. 1 024 byte
— Outputs, max. 1 024 byte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
DP slave
● GSD file http://www.ad.siemens.de/support in Product Support area
● Transmission rate, max. 12 Mbit/s
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD loops, max. 8
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV), 76 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● as client Yes; Via CP and loadable FB
● User data per job, max. See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)
S5 compatible communication
● supported Yes; via CP and loadable FC
Number of connections
● overall 16
● usable for PG communication 15
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 15
● usable for OP communication 15
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 15
● usable for S7 basic communication 12
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 12
● usable for routing 8; additional
S7 message functions
Number of login stations for message functions, max. 16; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
— of which status variables, max. 30
— of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— adjustable No
Interrupts/diagnostics/status information
Alarms No
Diagnostic functions No
Diagnostics indication LED
● Status indicator digital input (green) Yes
● Status indicator digital output (green) Yes
Potential separation
Potential separation digital inputs
● between the channels and backplane bus Yes
Potential separation digital outputs
● between the channels and backplane bus Yes
Permissible potential difference
between different circuits 75 V DC/60 V AC
Isolation
Isolation tested with 500 V DC
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 or higher and S7 Technology option package
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
Cycle time monitoring
● lower limit 1 ms
● upper limit 6 000 ms
● adjustable Yes
● preset 150 ms
Dimensions
Width 160 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 750 g
last modified: 09/07/2017