plc automation

Hotline

6ES7307-1BA01-0AA0

description:SIMATIC S7-300 stabilized power supply PS307 input: 120/230 V AC output: 24 V DC/2 A...
BASIC INFO

6ES7307-1BA01-0AA06ES7307-1BA01-0AA0

 
POWER SUPPLY PS307 24 V/2 A
SIMATIC S7-300 stabilized power supply PS307 input: 120/230 V AC output: 24 V DC/2 A
 
Input
Input 1-phase AC
Supply voltage
● 1 at AC Rated value 120 V
● 2 at AC Rated value 230 V
● Note Automatic range selection
Input voltage
● 1 at AC 85 ... 132 V
● 2 at AC 170 ... 264 V
Wide-range input No
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min. 20 ms; at Vin = 93/187 V
Rated line frequency 1 50 Hz
Rated line frequency 2 60 Hz
Rated line range 47 ... 63 Hz
Input current
● at rated input voltage 120 V 0.9 A
● at rated input voltage 230 V 0.5 A
Switch-on current limiting (+25 °C), max. 22 A
Duration of inrush current limiting at 25 °C
● maximum 3 ms
I2t, max. 1 A2·s
Built-in incoming fuse T 1.6 A/250 V (not accessible)
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: 3 A characteristic C
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.2 %
Residual ripple peak-peak, max. 50 mV
Residual ripple peak-peak, typ. 5 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 150 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 20 mV
Product function Output voltage adjustable No
Output voltage setting -
Status display Green LED for 24 V OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 2 s
Voltage rise, typ. 10 ms
Rated current value Iout rated 2 A
Current range 0 ... 2 A
Supplied active power typical 48 W
Short-term overload current
● on short-circuiting during the start-up typical 9 A
● at short-circuit during operation typical 9 A
Duration of overloading capability for excess current
● on short-circuiting during the start-up 90 ms
● at short-circuit during operation 90 ms
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced performance 2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 84 %
Power loss at Vout rated, Iout rated, approx. 9 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 0.8 %
Load step setting time 50 to 100%, typ. 0.5 ms
Load step setting time 100 to 50%, typ. 0.5 ms
Setting time maximum 1 ms
Protection and monitoring
Output overvoltage protection Additional control loop, shutdown at < 28.8 V, automatic restart
Current limitation 2.2 ... 2.6 A
Property of the output Short-circuit proof Yes
Short-circuit protection Electronic shutdown, automatic restart
Enduring short circuit current RMS value
● maximum 2 A
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class Class I
Leakage current
● maximum 3.5 mA
● typical 0.5 mA
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
Explosion protection ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455
FM approval Class I, Div. 2, Group ABCD, T4
CB approval No
Marine approval In S7-300 system
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation 0 ... 60 °C
— Note with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
● Supply input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded
● Output L+, M: 2 screw terminals each for 0.5 ... 2.5 mm2
● Auxiliary -
Width of the enclosure 40 mm
Height of the enclosure 125 mm
Depth of the enclosure 120 mm
Required spacing
● top 40 mm
● bottom 40 mm
● left 0 mm
● right 0 mm
Weight, approx. 0.4 kg
Product feature of the enclosure housing for side-by-side mounting Yes
Installation Can be mounted onto S7 rail
Mechanical accessories Mounting adapter for standard mounting rail (6EP1971-1BA00)
MTBF at 40 °C 2 320 078 h
Other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Pre:Siemens S7-300 PLC Next:6ES7307-1EA01-0AA0