plc automation

Hotline

SCHNEIDER LC1D25BD Contacor CONT. 11KW/400V LC1D25BD With Go

description:TeSys D Contactors - LC1D25BDContactorsTeSys D contactor - 3P(3 NO) - AC-3 - ...
BASIC INFO
SCHNEIDER LC1D25BD Contacor CONT. 11KW/400V LC1D25BD With Good Price  


TeSys D Contactors - LC1D25BD
Contactors
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil
  • Product availability
Stock - Normally stocked in distribution facility


1. Product Description:

Main
range    
TeSys
product name     
TeSys D
product or component type    
Contactor
device short name    
LC1D
contactor application 
Motor control
Resistive load
utilisation category    
AC-1
AC-3
AC-4
poles description
3P
pole contact composition 
3 NO
System Voltage 
<= 300 V DC power circuit
<= 690 V AC 25...400 Hz power circuit
[Ie] rated operational current   
25 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
40 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
motor power kW
11 kW at 380...400 V AC 50/60 Hz AC-3
15 kW at 500 V AC 50/60 Hz AC-3
15 kW at 660...690 V AC 50/60 Hz AC-3
5.5 kW at 220...230 V AC 50/60 Hz AC-3
11 kW at 415...440 V AC 50/60 Hz AC-3
5.5 kW at 400 V AC 50/60 Hz AC-4

SCHNEIDER LC1D25BD Contacor CONT. 11KW/400V LC1D25BD With Good Price  

motor power hp  
2 hp at 115 V AC 50/60 Hz 1 phase motors
7.5 hp at 200/208 V AC 50/60 Hz 3 phases motors
3 hp at 230/240 V AC 50/60 Hz 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz 3 phases motors
15 hp at 460/480 V AC 50/60 Hz 3 phases motors
20 hp at 575/600 V AC 50/60 Hz 3 phases motors
control circuit type    
DC standard
[Uc] control circuit voltage      
24 V DC
auxiliary contact composition 
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current   
40 A at <= 140 °F (60 °C) power circuit
10 A at <= 140 °F (60 °C) signalling circuit
Irms rated making capacity    
450 A at 440 V power circuit conforming to IEC 60947
140 A AC signalling circuit conforming to IEC 60947-5-1
250 A DC signalling circuit conforming to IEC 60947-5-1
rated breaking capacity   
450 A at 440 V power circuit conforming to IEC 60947
[Icw] rated short-time withstand current      
120 A <= 104 °F (40 °C) 1 min power circuit
240 A <= 104 °F (40 °C) 10 s power circuit
380 A <= 104 °F (40 °C) 1 s power circuit
50 A <= 104 °F (40 °C) 10 min power circuit
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
associated fuse rating      
40 A gG at <= 690 V coordination type 2 power circuit
63 A gG at <= 690 V coordination type 1 power circuit
10 A gG signalling circuit conforming to IEC 60947-5-1
average impedance  
2 mOhm at 50 Hz - Ith 40 A power circuit
[Ui] rated insulation voltage     
600 V power circuit certifications CSA
600 V power circuit certifications UL
690 V power circuit conforming to IEC 60947-4-1
690 V signalling circuit conforming to IEC 60947-1
600 V signalling circuit certifications CSA
600 V signalling circuit certifications UL
electrical durability    
1.65 Mcycles 25 A AC-3 at Ue <= 440 V
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
power dissipation per pole      
3.2 W AC-1
1.25 W AC-3
protective cover 
With
mounting support      
Plate
Rail
standards    
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
BV
CCC
CSA
DNV
GL
GOST
LROS (Lloyds register of shipping)
RINA
UL
connections - terminals   

SCHNEIDER LC1D25BD Contacor CONT. 11KW/400V LC1D25BD With Good Price  

Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
Power circuit: screw clamp terminals 1 cable(s) 0...0.02 in² (1.5...10 mm²) - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
Power circuit: screw clamp terminals 1 cable(s) 0...0.02 in² (2.5...10 mm²) - cable stiffness: flexible - without cable end
Power circuit: screw clamp terminals 2 cable(s) 0...0.02 in² (2.5...10 mm²) - cable stiffness: flexible - without cable end
Power circuit: screw clamp terminals 1 cable(s) 0...0.02 in² (1...10 mm²) - cable stiffness: flexible - with cable end
Power circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...6 mm²) - cable stiffness: flexible - with cable end
Power circuit: screw clamp terminals 2 cable(s) 0...0.02 in² (2.5...10 mm²) - cable stiffness: solid - without cable end

tightening torque

Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 22.12 lbf.in (2.5 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 22.12 lbf.in (2.5 N.m) - on screw clamp terminals - with screwdriver Philips No 2

operating time    
53.55...72.45 ms closing
16...24 ms opening
safety reliability level 
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

mechanical durability
30 Mcycles
operating rate     
3600 cyc/h at <= 140 °F (60 °C)
Complementary
coil technology   
Built-in bidirectional peak limiting diode suppressor
control circuit voltage limits    
0.1...0.25 Uc drop-out at 140 °F (60 °C), DC
0.7...1.25 Uc operational at 140 °F (60 °C), DC
time constant     
28 ms
inrush power in W     
5.4 W at 68 °F (20 °C)
hold-in power consumption in W   
5.4 W at 68 °F (20 °C)
auxiliary contacts type     
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1
signalling circuit frequency     
25...400 Hz
minimum switching current    
5 mA signalling circuit
minimum switching voltage    
17 V signalling circuit
non-overlap time
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
insulation resistance  
> 10 MOhm signalling circuit
Environment
IP degree of protection    
IP20 front face conforming to IEC 60529
protective treatment  
TH conforming to IEC 60068-2-30
pollution degree  
3
ambient air temperature for operation  
23...140 °F (-5...60 °C)
ambient air temperature for storage     
-76...176 °F (-60...80 °C)
permissible ambient air temperature around the device  
-40...158 °F (-40...70 °C) at Uc
operating altitude
9842.52 ft (3000 m) without derating in temperature
fire resistance    
1562 °F (850 °C) conforming to IEC 60695-2-1
flame retardance      
V1 conforming to UL 94
mechanical robustness    
Vibrations contactor open 2 Gn, 5...300 Hz
Vibrations contactor closed 4 Gn, 5...300 Hz
Shocks contactor closed 15 Gn for 11 ms
Shocks contactor open 8 Gn for 11 ms
height   
3.35 in (85 mm)
width     
1.77 in (45 mm)
depth    
3.98 in (101 mm)
product weight   
1.17 lb(US) (0.53 kg)
Ordering and shipping details
Category     
22345 - CTR,D-LINE,OPEN,NONREV-NEW
Discount Schedule    
I12
GTIN    
00785901207290
Nbr. of units in pkg.   
1
Package weight(Lbs)
1.29
Returnability
Y
Country of origin
ID
Offer Sustainability
Sustainable offer status   
Green Premium product
RoHS (date code: YYWW)     
Schneider Electric declaration of conformity
REACh 
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product end of life instructions      
Available
California proposition 65  
WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1     
Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer.
- - - - - - - More information     
For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 
12 months

SCHNEIDER LC1D25BD Contacor CONT. 11KW/400V LC1D25BD With Good Price  

2. Quality assurance:
 
100% original product, 100% quality assurance. 
If you find a fake. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt T/T, western union and paypal. If you can not trust us , you can choose to pay it via Aliexpress! 100% make your money safe!
3.SHIPPING:
We can shipping all over the world.via DHL,UPS,Fedex and EMS, the packaging is very safe and strong. if you have any special needs,please notify me.
It will take 3 to 7days to reach in your hands.
 

3.Contact details:

HONGKONG XIEYUAN TECH CO., LIMITED

Email/Skype:sales5@hkxytech.com/amy@whxyauto.com

Whatsapp/Mobile::+8613135657923
 
Web:www.hkxytech.com/www.plcs-automation.com
 
We mainly supply YOKOGAWA, SIEMENS, EMERSON, ABB, HONEYWELL, Allen Bradley,ENDRESS+ HAUSER, PEPPERL+FUCHS, FESTO, PARKER, FLUKE, WEIDMULLER, MTL, SMC,Schneider, Hirschmann,  ADVANTECH,MOXA, US Sensor, Mean Well, Murphy, YTC. Fisher, Auma, Rittal brands products. 
 
Any brand products inquiry, feel free to contact me.

 

Pre:Schneider Thermal-Magnetic motor circuit breakers GV2ME20 Te Next:Schneider LC1D32BD Contactor CONT. 15KW/400V LC1D32BD With G