MTL5575 1 Channel Isolation Barrier with RTD / THC Input, 20mA max+Alarm TEMPERATURE CONVERTER MTL5575 With Good Price



1.SPECIFICATIONS for MTL5575

 

· The MTL5575 converts a low-level dc signal from a temperature sensor
mounted in a hazardous area into a 4/20mA current for driving a safearea load
Software selectable features include linearisation, ranging,
monitoring, testing and tagging for all thermocouple types and 2-, 3-
or 4-wire RTDs

 

· (For thermocouple applications the HAZ-CJC plug on
terminals 1–3 includes an integral CJC sensor)
Configuration is carried out using a personal computer

 

· A single alarm output is provided and
may be configured for process alarm or to provide notice of early thermocouple failure

· One Number of channels

· Shipping weight: 1kg

 

The MTLx575 converts a low-level dc signal from a temperature sensor mounted in a hazardous area into a 4/20mA current for driving a safearea load. Software selectable features include linearisation, ranging, monitoring, testing and tagging for all thermocouple types and 2-, 3- or 4-wire RTDs. (For thermocouple applications the HAZ-CJC plug on terminals 1–3 includes an integral CJC sensor). Configuration is carried out using a personal computer. A single alarm output is provided and may be configured for process alarm or to provide notice of early thermocouple failure.

 

 

2. Number of channels:

One

Signal source

THC types J, K, T, E, R, S, B or N to BS 60584 and XK

mV input

RTDs 2/3/4-wire platinum to BS 60751

Pt 100, Pt 500, Pt 1000

Cu-50 & Cu-53

Ni 100/500/1000 DIN 43760

Location of signal source

Zone 0, IIC, T4-6 hazardous area

Division 1, Group A, hazardous location

Input signal range

–75 to +75mV, or 0 to 400Ω (0 to 1000Ω Pt & Ni sensors)

Input signal span

3 to 150mV, or 10 to 400Ω (10 to 1000Ω Pt & Ni sensors)

RTD excitation current

200µA nominal

Cold junction compensation

Automatic or selectable

Cold junction compensation error

≤ 1.0°C

Common mode rejection

120dB for 240V at 50Hz or 60Hz (500ms response)

Series mode rejection

40dB for 50Hz or 60Hz

Calibration accuracy (at 20°C)

(includes hysteresis, non-linearity and repeatability)

Inputs: (500ms response)

mV/THC: ± 15µV or ± 0.05% of input value

(whichever is greater)

RTD: ± 80mΩ

Output: ± 11µA

Temperature drift (typical)

Inputs:

mV/THC: ± 0.003% of input value/°C

RTD: ± 7mΩ/°C

Output: ± 0.6µA/°C

Example of calibration accuracy and temperature drift

(RTD input - 500ms response)

Span: 250Ω

Accuracy: ± (0.08/250 + 11/16000) x 100%

= 0.1% of span

Temperature drift: ± (0.007/250 x 16000 + 0.6) µA/°C

= ±1.0µA/°C

Safety drive on sensor failure

Upscale, downscale, or off

 


3. Quality assurance:
 

1. 100% original product, 100% quality assurance. 
If you find a fake. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt T/T, western union and paypal. If you can not trust us , you can choose to pay it via Aliexpress! 100% make your money safe!
3.SHIPPING:
We can shipping all over the world.via DHL,UPS,Fedex and EMS, the packaging is very safe and strong. if you have any special needs,please notify me.
It will take 3 to 7days to reach in your hands.


4.Contact details:


HONGKONG XIEYUAN TECH CO., LIMITED


Email/Skype:sales5@hkxytech.com


Whatsapp/Mobile::+8613135657923
 
Web:www.hkxytech.com
 

We mainly supply YOKOGAWA, SIEMENS, EMERSON, ABB, PR

ROCKWELL, HONEYWELL, ENDRESS+ HAUSER, PEPPERL+FUCHS, FESTO, PARKER, FLUKE, WEIDMULLER, MTL, SMC,Schneider, Hirschmann, ADVANTECH,MOXA, US Sensor, Mean Well, Murphy, allen Bradley, YTC, Fisher, Auma, Rittal and ect brands products.

 

Any brand products inquiry, feel free to contact me.

 

Pre:MTL5546Y ISOLATING DRIVER for 4–20mA HART® valve positione Next:MTL3022 SAFETY BARRIER/SOLENOID ALARM DRIVER/isolated shunt-